Fronius Symo 15.0-3 m Solar inverter SYMO-15.0-3-M 4.210.052
Fronius

Fronius Symo 15.0-3 m Solar inverter SYMO-15.0-3-M 4.210.052

Normaler Preis €2,233.53 €0.00
Fronius Symo 15.0-3 m Solar inverter SYMO-15.0-3-M

Maximum flexibility for tomorrow's applications.

With its performance classes of 3.0 to 20.0 kW, the trafolosis is Fronius Symo The three-phase inverter for each system size. Due to the high system voltage, the wide input voltage range and the two MPP trackers, the maximum flexibility in plant design is guaranteed. The standard connection to the Internet via WLAN or Ethernet as well as the simple integration of third-party components, make the Fronius Symo One of the most communicative inverters on the market.

Technical specifications



Input data Fronius Symo 15.0-3-M
Max. Input current
(IDC MAX1 / IDC MAX2)
33.0 A / 27.0 A
Max. Input current
(IDC MAX1 + IDC MAX2)
51.0 A
Max. Short circuit current module field (MPP1 / Mpp2)

49.5 A / 40.5 A

Min. Input voltage
(UDC min)
200 V
Supply starting voltage
(UDC Start)
200 V
Nominal input voltage (UDC, R) 600 V
Max. Input voltage
(UDC Max)
1,000 V
MPP voltage range
(UMpp min - umpp max)
320 - 800 V
Number of Mpp Tracker 2
Number of DC connections 3 + 3
Max. PV generator power (PDC Max) 22.5 kWpeak
Output data  
AC nominal power (PAC, R) 15,000 W
Max. Output power 15,000 VA
AC output current (IAC nom) 21.7 A
Mains connection (voltage range) 3 ~ NPE 400 V / 230 V or 3 ~ NPE 380V / 220V (+20% / -30%)
Frequency (frequency range) 50 Hz / 60 Hz (45 - 65 Hz)
Clank factor 1,5 %
Power factor (Cos φAC, R) 0 - 1 IND. / Cap.
GENERAL DATA  
Dimensions
(Height x width x depth)
725 x 510 x 225 mm
Weight 43.4 kg
Class IP 66
Protection class 1
Overvoltage category (DC / AC)1) 2 / 3
Night consumption <1 W
Inverter concept Trafolos
cooling Regulated air cooling
Assembly Indoor and outdoor assembly
Ambient temperature range -40 ° C to + 60 ° C
Permissible humidity 0% to 100%
Max. Height over sea level 2,000 m / 3,400 m (unrestricted / restricted voltage range)
Connection technology DC 6x DC + and 6x DC screw terminals 2.5 mm² - 16 mm²
Connection technology AC 5-pin AC screw terminals 2.5 mm² - 16 mm²
Certificates and Nursing Filling ÖVE / ÖNORM E 8001-4-712, DIN V VDE 0126-1-1 / A1, VDE AR ​​N 4105, IEC 62109-1 / -2, IEC 62116, IEC 61727, AS 3100, AS 4777-2, AS 4777 -3, CE 06-190, G83 / 2, UNE 206007-1, Si 4777, CEI 0-16, CEI 0-21, NRS 097
Efficiency  
Max. Efficiency 98,1 %
European Efficiency (ηu) 97,8 %
η at 5% pAC, R2)  91,2 / 94,8 / 92,3 % 
η at 10% pAC, R2) 93,4 / 96,0 / 94,4 %
η at 20% pAC, R2) 95,9 / 97,4 / 96,7 %
η at 25% pAC, R2) 96,2 / 97,6 / 97,0 %
η at 30% PAC, R2) 96,5 / 97,8 / 97,3 %
η at 50% pAC, R2) 96,9 / 98,1 / 97,7 %
η at 75% pAC, R2) 97,0 / 98,1 / 97,8 %
η at 100% pAC, R2) 97,0 / 98,1 / 97,7 %
MPP adaptation efficiency > 99,9 %
SAFETY DEVICES  
DC isolation measurement Yes
Overload Operating point shift, performance limitation
DC disconnector Yes
Reverse polarity protection Yes
Interface  
WLAN / Ethernet LAN Fronius Solar.web, Modbus TCP SunSpec, Fronius Solar API (JSON)
6 inputs and 4 digital inputs / outputs Connection to round control receiver
USB (type A socket) Data Logging, Inverter Update via USB Stick
2 x RS422 (RJ45 socket) Fronius Solar Net, Interface Protocol
Dispatch Energy management (potential-free relay output)
Datalogger and web server Integrated
External input Connection S0 counter / evaluation Overvoltage protection
RS485 Modbus RTU SUNSPEC or counter connection
1) According to IEC 62109-1. DIN rail for optional overvoltage protection type 2 available
2) And at uMpp min / UDC, R / Umpp max


The warranty conditions can be found under the tab Downloads

If you do not register online your new inverter after receipt, the minimum warranty of 2 years applies.

The activation of the new warranty services is carried out by a short registration www.solarweb.com

Instructions guarantee registration ...

5 years Fronius guarantee Plus (Material Guarantee + ServicePackage + Transport Package)

Downloads

Manufacturer's warranty:
Herstellergarantiebedingungen_FRONIUS.pdf

Data sheet:
Data sheet...

Diesen Artikel teilen